Roxspur Measurement and Control: For Good Measure RM&C LtdPlaton, Brearley, CT, Nulectrohms, SensitPhone 0870 22 00 724 or email sales@roxspur.com

For automatic sprinkler installations certain sizes of shunt orifice type water flowmeters have been approved to FOC Rules by the Loss Prevention Certification Board. These meters monitor flow in fire sprinkler systems, and have in-line filters, isolation valves and a safety housed indicator unit.

Specification
Flow Rate150-12500 L/min
Operating Temperature80.00 º
Operating Pressure12 BarG (at 20C)
Wetted MaterialsStainless Steel
Pipe size200.00mm
MaterialStainless steel plate mounted in a red polyester coated steel carrier ring
FlangesSuitable for BS 10 Table D or E. Other flange options available.
Filter Unit316SS filter inside TPX tube
Thickness38mm (replacement units available for 25mm models to order)
ValvesBrass nickel plated ball valves
TubeBorosilicate glass, l00mm scale
FloatStainless steel
Accuracy±5% of specified test flows
PipingPlated Copper impulse pipe with plated Brass connections
HousingRotatable polyester coated diecast
O Ring SealsNitrile rubber
Pressure Test30 Bar hydraulic
CertificationLPCB
Available Models
Flow Range (dm3/min)Nominal SizeCode
150-75050LPC - F1/5
300-150080LPC - F1/6
500-2500100LPC - F1/7
1000-5000150LPC - F1/8
2500-12500200LPC - F1/9